Weil-McLain CGa-8 Betriebsanleitung Seite 10

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 56
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 9
10 550-110-132/1298
CGi
Water Piping
Piping MULTIPLE ZONES:
Piping for use with REFRIGERATION SYSTEMS:
Water
chiller
Expansion tank
Circulator
Check
valve
Strainer
Boiler
Shut-off
valve
System
supply
System
return
Balancing
valve
301-067b
CONTD
FIGURE 4
Installing boiler on
REFRIGERATION SYSTEM
The boiler must be installed so the chilled medium
is piped in parallel with the heating boiler, using
appropriate valves to prevent the chilled medium
from entering boiler. Use piping as shown in
Figure 4.
If the boiler is connected to heating coils located in
air handling units where they can be exposed to
refrigerated air, gravity circulation during the
cooling cycle must be prevented with flow control
valves or other automatic means.
Piping for RADIANT HEATING SYSTEMS or CONVERTED GRAVITY SYSTEMS
c. Install balancing valves to adjust flow to dis-
tribute heat to all zones.
d. Separate relay is required for each circula-
tor.
4. Zoning with zone valves:
a. Install balancing valves to adjust flow to dis-
tribute heat to all zones.
b. Separate transformer is required to power
zone valves.
1. Follow instructions on pages 8 and 9 to install
near-boiler piping. (Also refer to Piping for radiant
heating systems or converted gravity systems if
applicable.)
2. See Figure 5A or 5B to complete installation.
3. Zoning with circulators:
a. Size each circulator to individual circuit re-
quirements.
b. Remove circulator on boiler.
Converted gravity (or steam) systems
Whenever possible, use the primary/secondary
piping shown in Figure 6A or 6B. This piping
design allows changing boiler flow rate without
affecting primary circuit flow rate.
If Figure 6A or 6B cannot be used, use the boiler
by-pass piping shown in Figure 7A or 7B.
You can also use the piping shown in Figure 8
(system by-pass) if the reduced flow rate in the
heating system will not cause heat distribution
problems.
Radiant heating systems
Preferably, use primary/secondary piping, as
shown in either Figure 6A or 6B. Alternatively, use
the method of either Figure 7A or 7B. Do not use
the piping of Figure 8, because this method does
not control radiant system supply temperature.
Failure to prevent low return water
temperature to the boiler could cause
corrosion of the boiler sections or burners, result-
ing in severe personal injury, death or substantial
property damage.
If radiant system tubing has no oxygen barrier, a
heat exchanger must be used.
Radiant heating system piping
should include a means of regulating
the boiler return water temperature AND the
system supply temperature (such as provided by
an injection pumping control). Boiler return water
temperature will be adequately controlled using
the methods shown in this manual provided the
system supply temperature is relatively constant.
DO NOT apply the methods in this manual if
the system is equipped with an outdoor reset
control. Instead, provide controls and piping
which can regulate the boiler return water
temperature at no less than 130 °F regardless
of system supply temperature. Contact your
Weil-McLain representative for suggested
piping and control methods. Failure to prevent
cold return water temperature to the boiler
could cause corrosion damage to the sections
or burners, resulting in possible severe
personal injury, death or substantial property
damage.
Seitenansicht 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 55 56

Kommentare zu diesen Handbüchern

Keine Kommentare