GAS-FIRED WATER BOILER SERIES 1 & 2
Control supplement & Service guide
Troubleshooting (continued)
Instructions in this supplement are based
on factory default parameter settings.
HARD LOCKOUT condition [Display flashes first digit, “E” and last two digits (code)]
02 Ignition failed through 5 attempts:
3PARKOCCURSBUTNOmAME:
4HISSECTIONCONTINUEDFROMPREVIOUSPAGE
11
Remove condensate drain and check drain fitting on bottom of heat exchanger and
condensate trap for restriction.
If restricted, clean and let condensate water out. s
Re-connect and fire boiler.s
12
Clean the heat exchanger — perform the boiler complete maintenance procedures
beginning on page 33 of this guide.
13
See Ultra Boiler manual or the instructions in this guide for procedure to disconnect
gas valve from venturi.
Inspect venturi gas line to verify there are no obstructions. s
Reinstall gas valve.s
14
Check for possible flue gas recirculation at vent/air terminations or inside boiler hous-
ing. Look for signs of moisture, corrosion in the venturi or water dripping from the
burner.
15
If gas valve is powered, gas flows when activated, and above have been verified, replace
the gas valve and retry.
02 Ignition failed through 5 attempts:
&LAMEOCCURSBUTmAMESIGNAL
STRENGTHISLOW
( less than 4 vdc
between low voltage terminal strip
terminal 9 and ground):
1
Inspect flame per procedure in Ultra Boiler manual, at low fire and high fire rates.
2
Remove and inspect/clean ignition electrode per Ultra Boiler Manual. Clean white oxides
if necessary. Replace ignition electrode if in poor condition or cannot be cleaned.
3
Inspect and clean burner if necessary — perform the boiler complete maintenance
procedures beginning on page 33 of this guide.
Replace burner if not in good condition.s
4
Check gas flow rate at gas meter with boiler at high fire (see Ultra Boiler manual for
procedure to force boiler to high fire).
5
If input is not within about 10% of boiler rating, replace gas valve.
Note that the length of the vent/air piping will affect boiler firing rate, with longer s
piping causing lower inputs.
6
Check ground wire and connections from ground terminal strip to heat exchanger access
cover and from ground terminal strip to X1-6 terminal on the wiring harness.
Use ground continuity meter to verify good ground path.s
7
Follow procedure in Ultra Boiler manual to inspect and clean ignition electrode.
Replace ignition electrode if necessary.s
8
If above does not correct problem, replace control module.
03 Ignition failure or gas valve
electrical problem
1
If error occurs before boiler tries for ignition, problem may be gas valve connection or
harness. Measure continuity of gas valve harness through outer 2 pins of connector.
2
Measure resistance between outer two pins on gas valve — should be approximately 50
ohms. Resistance from each pin to ground must be infinity.
3
If error occurs after 5 ignition retries, E-03 indicates same condition as E-02. Refer to
E-02 troubleshooting.
4
Replace control module.
&IGURE Troubleshooting procedures — when display shows hard lockout code (continued)