Part number GL-E223-ADOC 0311
This manual must only be used by a qualified heating installer/service technician. BEFORE installing, read all instruc-
tions in this manual and all other information shipped with the water heater. Perform steps in the order given. Failure
to comply could result in severe personal injury, death or substantial property damage.
• Installation
• Startup
• Maintenance
• Parts
Product Manual
Indirect-Fired Water Heaters
User — Read important user safety information found on page 3, page 24 and page 25. Installation and service should
only be performed by a qualified service technician. Retain this manual for future reference.
®
®
TM
Seitenansicht 0
1 2 3 4 5 6 ... 43 44

Inhaltsverzeichnis

Seite 1 - Product Manual

Part number GL-E223-ADOC 0311 This manual must only be used by a qualified heating installer/service technician. BEFORE installing, read all instruc-t

Seite 2 - Contents

AQUA PLUS indirect-fired water heaters — Product ManualRecirculation (continued)ComponentsCirculator (Figure 6, item 1)1. Little flow is required to m

Seite 3 - Please read before proceeding

AQUA PLUS indirect-fired water heaters — Product ManualFigure 7 Zoning with circulators — direct-connected system pipingNotes• Place circulators at

Seite 4 - Pre-installation

AQUA PLUS indirect-fired water heaters — Product ManualBoiler-side piping (continued)Figure 8 Zoning with circulators — primary/secondary system pipi

Seite 5

AQUA PLUS indirect-fired water heaters — Product ManualBoiler-side piping (continued)Figure 9 Zoning with zone valves — direct-connected system pipin

Seite 6 - Domestic water piping

AQUA PLUS indirect-fired water heaters — Product ManualBoiler-side piping (continued)Figure 10 Zoning with zone valves — primary/secondary system pip

Seite 7

AQUA PLUS indirect-fired water heaters — Product ManualBoiler-side piping (continued)Figure 11 Dedicated single-boiler pipingNotes• Place circulator

Seite 8

AQUA PLUS indirect-fired water heaters — Product ManualBoiler-side piping (continued)Figure 12 Multiple water heaters — domestic water pipingFigure 1

Seite 9

AQUA PLUS indirect-fired water heaters — Product ManualBoiler-side piping (continued)Figure 14 Multiple water heaters and dedicated multiple boilers

Seite 10 - Recirculation

AQUA PLUS indirect-fired water heaters — Product ManualConnecting to a low-pressure steam boilerSpecial considerationsWhen designing steam and domesti

Seite 11 - Boiler-side piping

AQUA PLUS indirect-fired water heaters — Product ManualConnecting to a low-pressure steam boiler (continued)Figure 16 Low pressure steam boiler appli

Seite 12

AQUA PLUS indirect-fired water heaters — Product ManualContentsPlease read before proceeding 3When servicing water heater . . . . . . . . .

Seite 13

AQUA PLUS indirect-fired water heaters — Product ManualBoiler-side wiring and controls Electrical shock hazard — Can cause severe personal injury, de

Seite 14

AQUA PLUS indirect-fired water heaters — Product ManualWiring — zoning with circulatorsNotes• Also refer to the WMCR manual and Weil-McLain Boiler

Seite 15

AQUA PLUS indirect-fired water heaters — Product ManualWiring — zoning with zone valvesNotes• Also refer to the WMZV manual and Weil-McLain Boiler

Seite 16

AQUA PLUS indirect-fired water heaters — Product ManualWater heater filling and start-up The installation and water chemistry must meet the req

Seite 17

AQUA PLUS indirect-fired water heaters — Product Manual Hot Water Can Scald!• Water heated to temperature for clothes washing, dish washing and other

Seite 18 - Special considerations

AQUA PLUS indirect-fired water heaters — Product ManualWater heater maintenance Boiler water — read and comply with all requirements under “Boiler wa

Seite 19 - Filling the piping

AQUA PLUS indirect-fired water heaters — Product ManualWater heater maintenance (continued)and their frequencies, including any not listed in the

Seite 20

AQUA PLUS indirect-fired water heaters — Product ManualTroubleshootingPreparation for troubleshootingTools needed Electrical meter to measure voltage

Seite 21 - Part number GL-E223-ADOC 0311

AQUA PLUS indirect-fired water heaters — Product ManualTroubleshooting (continued)Insufficient hot water1 Undersized water heater?2 Boiler system imp

Seite 22

AQUA PLUS indirect-fired water heaters — Product ManualTroubleshooting (continued)1 Undersized water heater? • There are many methods of sizing vari

Seite 23

AQUA PLUS indirect-fired water heaters — Product ManualPlease read before proceeding Failure to adhere to the guidelines on this page can result in s

Seite 24 - Hot Water Can Scald!

AQUA PLUS indirect-fired water heaters — Product ManualTroubleshooting (continued)• Is the circulator between the boiler and the water heater properl

Seite 25 - Water heater maintenance

AQUA PLUS indirect-fired water heaters — Product ManualTroubleshooting (continued)4 Check boiler operating temperatures. • If possible, increase the

Seite 26

AQUA PLUS indirect-fired water heaters — Product ManualTroubleshooting (continued)Excessive domestic water temperature1 Reduce stacking. • Excessive

Seite 27 - Troubleshooting

AQUA PLUS indirect-fired water heaters — Product ManualTroubleshooting (continued)Boiler relief valve lifting or weeping1 Undersized expansion tank?

Seite 28

AQUA PLUS indirect-fired water heaters — Product ManualTroubleshooting (continued)Temperature/pressure relief valve lifting or weeping1 Undersized or

Seite 29

AQUA PLUS indirect-fired water heaters — Product ManualTroubleshooting (continued)Water on the floor near the tank1 Check for leaks from sources other

Seite 30

AQUA PLUS indirect-fired water heaters — Product ManualTroubleshooting (continued)Rapid decay of magnesium anode1 Anodes last less than two years T

Seite 31

AQUA PLUS indirect-fired water heaters — Product ManualWater quality problems1 Water smells like “rotten eggs.” • The most common cause of water to

Seite 32

AQUA PLUS indirect-fired water heaters — Product Manual• This is similar to the reaction that occurs as air bubbles form on the walls of a pan shortl

Seite 33

AQUA PLUS indirect-fired water heaters — Product ManualItem DescriptionSize/ModelAQUA PLUSWeil-McLain Part Number1Magnesium anode replacement kit (inc

Seite 34

AQUA PLUS indirect-fired water heaters — Product ManualPre-installationFigure 1 Clearance recommendationsCodes1. Installation must conform with inst

Seite 35

AQUA PLUS indirect-fired water heaters — Product ManualAHRI ratingsModel AQUA PLUSAHRI certified ratings180°F boiler water entering | 58°F to 135°F d

Seite 36

AQUA PLUS indirect-fired water heaters — Product ManualRatings with 200°F boiler supply water For water heater to achieve the rated performance below

Seite 37

AQUA PLUS indirect-fired water heaters — Product ManualRatings with 190°F boiler supply water For water heater to achieve the rated performance below

Seite 38

AQUA PLUS indirect-fired water heaters — Product ManualRatings with 180°F boiler supply water For water heater to achieve the rated performance below

Seite 39 - Replacement parts

AQUA PLUS indirect-fired water heaters — Product ManualDimensionsFigure 25 Dimensions and ratings — AQUA PLUS indirect-fired water heatersModelAQUA PL

Seite 40 - AHRI ratings

AQUA PLUS indirect-fired water heaters — Product ManualPre-installation (continued) Hot Water Can Scald!• Water heated to temperature for clothes was

Seite 41 - DHW 50°F to 115°F

AQUA PLUS indirect-fired water heaters — Product ManualDomestic water pipingFigure 2 DHW pipingPiping overview THERMAL EXPANSION TANK — If a bac

Seite 42

AQUA PLUS indirect-fired water heaters — Product ManualDomestic water piping (continued)LEGEND for Figure 2, page 6 Domestic water supplied to fixture

Seite 43

AQUA PLUS indirect-fired water heaters — Product ManualRecirculation Massachusetts code applications require recircu-lation piping or heat-traced pip

Seite 44 - Dimensions

AQUA PLUS indirect-fired water heaters — Product ManualRecirculation (continued)Figure 4 Time lag to obtain hot water at fixture for branch lengths of